Requirements:
Luminaire
wattage incorporated into the installed interior lighting power shall be
determined in accordance with the following criteria:
- The wattage of incandescent or tungsten-halogen luminaires with
medium screw base sockets and not containing permanently installed
ballasts shall be the maximum labeled wattage of the luminaire.
- The wattage of luminaires with permanently installed or remote
ballasts or transformers shall be the operating input wattage of the
maximum lamp/auxiliary combination based on values from the
auxiliary manufacturer’s literature or recognized testing
laboratories.
- The wattage of line-voltage lighting track and plug-in busway
that allow the addition and/or relocation of luminaires without
altering the wiring of the system shall be the specified wattage of
the luminaires included in the system with a minimum of 30 W/linear ft.
- The wattage of low-voltage lighting track, cable conductor, rail
conductor, and other flexible lighting systems that allow the
addition and/or relocation of luminaires without altering the wiring
of the system shall be the specified wattage of the transformer
supplying the system.
- The wattage of all other miscellaneous lighting equipment shall
be the specified wattage of the lighting equipment.
Exceptions:
None. |